Square D™ TeSys® LC1F150 3-Phase IEC Contactor With Coil, 600 VAC V Coil, 150 A, 3NO Contact, 3 Poles
LC1F150
MFG #: LC1F150
Requires Quote
Square D™ TeSys® IEC Contactor, 3-Phase, Series: LC1F, 600 VAC Coil, 150 A Maximum Load Current, 100 kW Coil, 3 Pole, 50/60 Hz Frequency, 22/8 W Wattage, Non-Reversing Contact, 3NO Contact Configuration, 600 VAC, 150 A Inductive, 250 A Resistive Contact, Bolt-On/Lug Terminal, IP20 Enclosure, 10000000 cycles Operating Cycles, -5 to 55 deg C Operating, Panel Mounting, 6.44 in W x 6.73 in D x 6.69 in H Dimensions
- 8 kv-rated impulse withstand voltage
- III overvoltage category
- 250 a at 104 deg f conventional-free air thermal current
- 1200 a conforming to IEC 60947-4-1 rated breaking capacity
- 160 a aM at 440 V/250 a gG at 440 V associated fuse rating
- 0.35 mohm at 50 Hz to Ith 200 a average impedance
- 1000 V conforming to IEC 60947-4-1/1500 V conforming to VDE 0110 group c rated insulation voltage
- 88.5 in-lb tightening torque power circuit
- 23 to 35 ms closing/5 to 15 ms opening operating time
- 2400 cycles/hr at 131 deg f operating rate
- 660 VA at 68 deg f 60 Hz inrush power
- 55 VA at 68 deg f 60 Hz hold-in power consumption
- 12 to 16 W heat dissipation
- TH protective treatment
- -40 to 158 deg f permissible ambient air temperature around the device
- 9842.52 ft without derating in temperature operating altitude
- Vibrations contactor closed 6 gn, 5 to 300 Hz/shocks contactor open 9 gn for 11 ms/vibrations contac
- 65 kW at 1000 vac 50/60 Hz AC-3, 40 kW at 220 to 230 vac 50/60 Hz AC-3, 75 kW at 380 to 400 vac 50/6
- 22 kW at 400 vac 50/60 Hz AC-4, 80 kW at 415 vac 50/60 Hz AC-3, 80 kW at 440 vac 50/60 Hz AC-3, 100
- 22 W (AC-1), 8 W (AC-3) power dissipation per pole
8 kv-rated impulse withstand voltage
III overvoltage category
250 a at 104 deg f conventional-free air thermal current
1200 a conforming to IEC 60947-4-1 rated breaking capacity
160 a aM at 440 V/250 a gG at 440 V associated fuse rating
0.35 mohm at 50 Hz to Ith 200 a average impedance
1000 V conforming to IEC 60947-4-1/1500 V conforming to VDE 0110 group c rated insulation voltage
88.5 in-lb tightening torque power circuit
23 to 35 ms closing/5 to 15 ms opening operating time
2400 cycles/hr at 131 deg f operating rate
660 VA at 68 deg f 60 Hz inrush power
55 VA at 68 deg f 60 Hz hold-in power consumption
12 to 16 W heat dissipation
TH protective treatment
-40 to 158 deg f permissible ambient air temperature around the device
9842.52 ft without derating in temperature operating altitude
Vibrations contactor closed 6 gn, 5 to 300 Hz/shocks contactor open 9 gn for 11 ms/vibrations contactor open 2 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms mechanical robustness
65 kW at 1000 vac 50/60 Hz AC-3, 40 kW at 220 to 230 vac 50/60 Hz AC-3, 75 kW at 380 to 400 vac 50/60 Hz AC-3, 90 kW at 500 vac 50/60 Hz AC-3 motor power
22 kW at 400 vac 50/60 Hz AC-4, 80 kW at 415 vac 50/60 Hz AC-3, 80 kW at 440 vac 50/60 Hz AC-3, 100 kW at 660 to 690 vac 50/60 Hz AC-3 motor power
22 W (AC-1), 8 W (AC-3) power dissipation per pole